| » View sub category/Products |
|
|
UPS Maintenance Bypass Panels
-
External full maintenance bypass panels, 3Ø
-
2 breaker, 3 breaker & custom configurations
-
UL 489 circuit protection, UL1778 UPS application
-
NEMA 1 wall & floor mountings
-
Make-before-break design; Kirk-Key© type safety interlocks; solenoid key release (SKRU) as standard
-
Shunt Trip & EPO interface as standard
-
208, 360, 480 50/60Hz VAC operation
-
150A-1200A for 30kVA to 750kVA UPS in stock
-
expanded capacities available upon request
400A 3CB MBP Oultine (typical) 
400A 3CB MBP Wiring Diagram 
Bypass Sizing Guide 
|

|
|
|
|
|
|
Wall-Mount Nema Configuration Bypass Panels
|
|
Make-before-break; Kirk-Key, Shunt Trip, Aux Contacts, SKRU. 35kAIC standard Free-standing floor
|
|
when input voltage to UPS is different from output, consult with SBS engineering services
|
|
kVA
|
Voltage
|
Amperage
|
Round-Up
|
Breaker
|
kAIC
|
Height
|
Width
|
Depth
|
Weight
|
|
|
|
Input
|
Output
|
"AF"
|
"AT"
|
Quan
|
|
Inches
|
Inches
|
Inches
|
LBS.
|
|
|
30
|
208
|
208
|
150
|
104
|
2
|
65
|
74.2
|
31
|
14
|
382
|
|
|
|
208
|
208
|
150
|
104
|
3
|
65
|
74.2
|
31
|
14
|
389
|
|
|
|
480
|
480
|
100
|
45
|
2
|
35
|
74.2
|
31
|
14
|
382
|
|
|
|
480
|
480
|
100
|
45
|
3
|
35
|
74.2
|
31
|
14
|
389
|
|
|
40
|
208
|
208
|
150
|
139
|
2
|
65
|
74.2
|
31
|
14
|
382
|
|
|
|
208
|
208
|
150
|
139
|
3
|
65
|
74.2
|
31
|
14
|
389
|
|
|
|
480
|
480
|
100
|
60
|
2
|
35
|
74.2
|
31
|
14
|
382
|
|
|
|
480
|
480
|
100
|
60
|
3
|
35
|
74.2
|
31
|
14
|
389
|
|
|
50
|
208
|
208
|
250
|
173
|
2
|
65
|
74.2
|
31
|
14
|
382
|
|
|
|
208
|
208
|
250
|
173
|
3
|
65
|
74.2
|
31
|
14
|
389
|
|
|
|
480
|
480
|
150
|
75
|
2
|
35
|
74.2
|
31
|
14
|
382
|
|
|
|
480
|
480
|
150
|
75
|
3
|
35
|
74.2
|
31
|
14
|
389
|
|
|
65
|
208
|
208
|
250
|
226
|
2
|
65
|
74.2
|
31
|
14
|
382
|
|
|
|
208
|
208
|
250
|
226
|
3
|
65
|
74.2
|
31
|
14
|
389
|
|
|
|
480
|
480
|
150
|
98
|
2
|
35
|
74.2
|
31
|
14
|
382
|
|
|
|
480
|
480
|
150
|
98
|
3
|
35
|
74.2
|
31
|
14
|
389
|
|
|
80
|
208
|
208
|
400
|
278
|
2
|
65
|
82.4
|
40
|
14
|
560
|
|
|
|
208
|
208
|
400
|
278
|
3
|
65
|
82.4
|
40
|
14
|
569
|
|
|
|
480
|
480
|
150
|
120
|
2
|
35
|
74.2
|
31
|
14
|
382
|
|
|
|
480
|
480
|
150
|
120
|
3
|
35
|
74.2
|
31
|
14
|
389
|
|
|
100
|
208
|
208
|
400
|
347
|
2
|
65
|
82.4
|
40
|
14
|
560
|
|
|
|
208
|
208
|
400
|
347
|
3
|
65
|
82.4
|
40
|
14
|
569
|
|
|
|
480
|
480
|
150
|
150
|
2
|
35
|
74.2
|
31
|
14
|
382
|
|
|
|
480
|
480
|
150
|
150
|
3
|
35
|
74.2
|
31
|
14
|
389
|
|
|
130
|
208
|
208
|
600
|
451
|
2
|
65
|
90.7
|
40
|
14
|
597
|
|
|
|
208
|
208
|
600
|
451
|
3
|
65
|
90.7
|
40
|
14
|
604
|
|
|
|
480
|
480
|
250
|
195
|
2
|
35
|
74.2
|
31
|
14
|
382
|
|
|
|
480
|
480
|
250
|
195
|
3
|
35
|
74.2
|
31
|
14
|
389
|
|
|
160
|
208
|
208
|
600
|
555
|
2
|
65
|
90.7
|
40
|
14
|
597
|
|
|
|
208
|
208
|
600
|
555
|
3
|
65
|
90.7
|
40
|
14
|
604
|
|
|
|
480
|
480
|
250
|
241
|
2
|
35
|
74.2
|
31
|
14
|
382
|
|
|
|
480
|
480
|
250
|
241
|
3
|
35
|
74.2
|
31
|
14
|
389
|
|
|
225
|
208
|
208
|
800
|
781
|
2
|
65
|
90.7
|
40
|
14
|
597
|
|
|
|
208
|
208
|
800
|
781
|
3
|
65
|
90.7
|
40
|
14
|
604
|
|
|
|
480
|
480
|
400
|
338
|
2
|
35
|
82.4
|
40
|
14
|
560
|
|
|
|
480
|
480
|
400
|
338
|
3
|
35
|
82.4
|
40
|
14
|
569
|
|
|
300
|
480
|
480
|
600
|
451
|
2
|
35
|
90.7
|
40
|
14
|
597
|
|
|
|
480
|
480
|
600
|
451
|
3
|
35
|
90.7
|
40
|
14
|
604
|
|
|
400
|
480
|
480
|
600
|
601
|
2
|
35
|
90.7
|
40
|
14
|
597
|
|
|
|
480
|
480
|
600
|
601
|
3
|
35
|
90.7
|
40
|
14
|
604
|
|
|
500
|
480
|
480
|
800
|
752
|
2
|
65
|
90.7
|
40
|
14
|
608
|
|
|
|
480
|
480
|
800
|
752
|
3
|
65
|
90.7
|
40
|
14
|
619
|
|
|
625
|
480
|
480
|
1200
|
940
|
2
|
65
|
90.7
|
40
|
14
|
608
|
|
|
|
480
|
480
|
1200
|
940
|
3
|
65
|
90.7
|
40
|
14
|
619
|
|
|
750
|
480
|
480
|
1200
|
1128
|
2
|
65
|
90.7
|
40
|
14
|
608
|
|
|
|
480
|
480
|
1200
|
1128
|
3
|
65
|
90.7
|
40
|
14
|
619
|
|
|
|
Most
|
Common |
Sizes
|
|
|
|
"AF" Frame Size- Trip Setting is Less
|
|
|
|
|
Main Battery Disconnects
- 24vdc - 480vdc nominal dc bus
- Circuit breaker (UL489) or fusible
- 100A- 4000A
- Shunt trip (120vac), UVR(24v) & EPO (n/c) interface as standard
- Other voltages available upon request
- NEMA 1 wall/floor mountings
|
 |
One Line MBD Dwg (typical)  |
|
| |
|
| SBS MAIN BATTERY DISCONNECT SELECTION & PRICING |
| |
| DC AMPS |
NOMINAL |
CONFIGURATION NUMBER |
UNDER-VOLTAGE |
POLES |
ENCLOSURE |
AUX |
SHUNT |
|
|
| Vdc BUS |
|
RELEASE |
|
|
CONTACT |
TRIP |
|
|
| 100 |
<240v |
SEDA24AT0150TE100-ST-UV-B1 |
24vdc/vac |
2 |
NEMA1 |
1 |
120/60 |
|
|
| 150 |
(120 cells) |
SEDA24AT0150TE150-ST-UV-B1 |
24vdc/vac |
2 |
NEMA1 |
1 |
120/60 |
|
|
| 250 |
240 vdc |
SFHA24AT0250SF250-ST-UV-B1 |
24vdc/vac |
2 |
NEMA1 |
1 |
120/60 |
|
|
| 400 |
|
SGHA26AT0400SG400-ST-UV-B1 |
24vdc/vac |
2 |
NEMA1 |
1 |
120/60 |
|
|
| 600 |
|
SGHA26AT0600SG600-ST-UV-B1 |
24vdc/vac |
2 |
NEMA1 |
1 |
120/60 |
|
|
| 800 |
|
SGHA26AT0800SG600-ST-UV-B1 |
24vdc/vac |
2 |
NEMA1 |
1 |
120/60 |
|
|
| 1200 |
|
SGHA26AT01200SK1200-ST-UV-B1 |
24vdc/vac |
2 |
NEMA1 |
1 |
120/60 |
|
|
| |
|
|
|
|
|
|
|
|
|
| 100 |
>240v |
SEHA36AT0150TE100-ST-UV-B1 |
24vdc/vac |
3 |
NEMA1 |
1 |
120/60 |
|
|
| 150 |
(240 cells) |
SEHA36AT0150TE150-ST-UV-B1 |
24vdc/vac |
3 |
NEMA1 |
1 |
120/60 |
|
|
| 250 |
480vdc |
SFHA36AT0250SF250-ST-UV-B1 |
24vdc/vac |
3 |
NEMA1 |
1 |
120/60 |
|
|
| 400 |
|
SGHA36AT0400SG400-ST-UV-B1 |
24vdc/vac |
3 |
NEMA1 |
1 |
120/60 |
|
|
| 600 |
|
SGHA36AT0600SG600-ST-UV-B1 |
24vdc/vac |
3 |
NEMA1 |
1 |
120/60 |
|
|
| 800 |
|
SGHA36AT0800SG600-ST-UV-B1 |
24vdc/vac |
3 |
NEMA1 |
1 |
120/60 |
|
|
| 1200 |
|
SGHA36AT1200SK1200-ST-UV-B1 |
24vdc/vac |
3 |
NEMA1 |
1 |
120/60 |
|
|
| |
|
|
|
|
|
|
|
|
|
| All battery disconnects are in UL NEMA 1 enclosure with a UL890 circuit breaker rated for 250vdc nominal, and have both a 120/60 Shunt Trip Module (Liebert & Default) or a 24v S.T. Module (Powerware, Specify), 24Vac/dc Under-Voltage Release Module (MGE, Mitsubishi, Default) and one auxilliary contact N/C, (Default). Two pole circuit breakers are suitable for battery systems of 125 cells or less. Three pole breakers are designed for systems in excess of 125 cells and are to be "Series Connected" to achieve a 500vdc nominal rating. Series connection requires that the positive conductor be routed through 2 of the 3 breaker poles. Should you have any questions about this standard dc wiring practice, please contact SBS engineering services at 800-554-2243, xt 309; or email sbs@sbsbattery.com. ALWAYS CHECK UPS I&O MANUAL FOR PROPER DC BREAKER RATING. Consult factory for other configurations. |
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
Custom Switchgear
- generator paralleling
- automatic transfer switches (ATS)
- protective saftey relay design
|
- cogeneration, load shedding
- load sharring
- circuit protection coordination
- programmable controllers (PLCs)
- power metering
- SCADA interface
|
 |
 |
| |
|
|
|