SBS-1110S: Battery Capacity Tester

Constant Current DC Load Bank
125 Vdc 0–100 Amp

The only way to know your stationary batteries will perform to specification is to test the batteries’ capacity with a DC load tester.

 

NERC standard PRC-005-2 requires that Vented Lead-Acid and Nickel Cadmium systems be discharge tested every six years and Valve Regulated Lead-Acid (VRLA) batteries be tested every three years.

 

IEEE recommends load testing stationary flooded / vented lead-acid and Ni-Cad stationary batteries every 5 years and VRLA batteries every 12-18 months.

 

 

The SBS-1110S constant current load banks are an easy and affordable way to perform accurate IEEE450 (Vented Lead-Acid), IEEE1106 (Ni-Cad) and IEEE1188 (VRLA) load tests.

 

These units are quick and easy to set up. They display the voltage, current and Ah removed during the test. Since this is a constant current load bank, the user also does not have to constantly adjust the current during the test like many other load banks.

 

These load banks come standard with multiple auto-stop settings and built-in protection to ensure that the batteries are never damaged due to over discharge.

 

Built-in Protection:

  • Audible alarm
  • Warning on LED screen
  • High temperature shutdown
  • High voltage shutdown
  • Over load protection

 

Features:

  • Constant current load bank holds the current set throughout the test
  • LED screen displays real time voltage, discharge current and Ah removed
  • Units can be paralleled with the SBS-8400 if data acquisition/individual cell monitoring required
  • Easily adjust settings electronically

3 adjustable stop points:
• End system voltage
• Discharge time
• Discharge capacity (Ah)

DC load bank SBS-1110S battery capacity tester 

 

Resources:

  - SBS-1110S Data Sheet

  - SBS-1110S User's Manual

 

S-Series Battery Load Banks by SBS Battery Video

Video: Battery Capacity Tester /DC Load Banks (S-Series)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Construction

Display LCD (128 x 64 pixels)
During discharge: real time voltage / current / test time / Ah discharged
Input User can set: end system voltage / test time / Capacity discharged (Ah)
Test Type Unit controls the current so it stays where it is set throughout the test
Protection Over heat / Over load / Over voltage protection with audible alarm and screen warning
Power Supply DC power supply (from tested battery)
DC Cables Included - 9 ft long

 

 

 

Specifications

Part No.

DC Voltage Range

DC Current Range (Amps)

Dimensions
L x W x H (in.)

Weight (lbs.)

SBS-1110S

90 - 150 Vdc

0 - 100A

25 x 9 x 15

44.0

 

 

Ordering Information

Part No. Description
SBS-1110S 125 Vdc 0-100Amp Constant Current Load Bank

 

 

Accessory Ordering Information

Part No. Description
BCT110/220 - 1000 1000 Watt Voltage Transformer 110/220 Vac 50/60Hz
8400-600A 600 DC Current Clamp