SBS-4830S: Battery Capacity Tester

Constant Current DC Load Bank
24 Vdc 0–150 Amp / 48 Vdc 0–300 Amp

The only way to know if your stationary batteries will perform to specification is to test them regularly.

NERC standard PRC-005-2 requires that vented lead acid and nickel cadmium (NiCd) systems be discharge tested every six (6) years and valve regulated lead acid (VRLA) batteries every three (3) years. IEEE recommends load testing stationary flooded/vented lead acid and NiCd stationary batteries every five (5) years and VRLA batteries every 12–18 months.

The SBS-4830S constant current load bank is an affordable way to perform easy and accurate IEEE450 (vented lead acid), IEEE1106 (NiCd) and IEEE1188 (VRLA) load tests.

These units are quick and easy to set up. They display the voltage, current and Ah removed from the string during the test. Since this is a constant current load bank, the user also does not have to adjust the current during the test.

These load banks come standard with multiple adjustable stop points and built-in protection to ensure that the batteries are never damaged due to over-discharge.

Built-in Protection:

  • Audible alarm
  • Warning on LCD screen
  • High temperature shutdown
  • High voltage shutdown
  • Overload protection

Features:

  • Many unit options with wide voltage and current range
  • Automatically discharges batteries unmanned without danger of over-discharging
  • Continuously holds the current set throughout the test
  • LCD screen displays real time voltage, discharge current and capacity/Ah removed
  • Test parameters are adjustable during test without stopping test
    • End system voltage
    • Discharge time
    • Discharge capacity (Ah)
  • Units can be slaved with the SBS-8400 and/or other load banks to increase amp draw

3 adjustable stop points:

  • End system voltage
  • Discharge time
  • Discharge capacity (Ah)

battery discharge tester 24-250 Vdc battery systems

Resources:

  - SBS-4830S Data Sheet

  - User's Manual

S-Series Battery Load Banks by SBS Battery Video

Video: Battery Capacity Tester / DC Load Banks (S-Series)

Technical Data

Display LCD (128 x 64 pixels)
Input During discharge: real time voltage / current / test time / capacity discharged (Ah)
User can set: end system voltage / test time / capacity discharged (Ah)
Test Type Unit holds the set current throughout the test
Protection Overheat / Overload / Over voltage protection with audible alarm and screen warning
Power Supply SBS-4830S uses DC power supply (from tested battery)
125 and 250 Vdc units use AC power supply (110 Vac 60 Hz)
DC Cables Included, 9 ft. long

Specifications

Part No.

DC Voltage Range

DC Current Range (Amps)

Dimensions
L x W x H (in.)

Weight (lb.)

SBS-4830S

20–40 Vdc
40–60 Vdc
0–150 A
0–300 A
26 x 9 x 16 40

Ordering Information

Part No. Description
SBS-4830S 24 Vdc 0–150 Amp / 48 Vdc 0–300 Amp Constant Current Load Bank

Accessory Ordering Information

Part No. Description
8400-600A 600 DC Current Clamp
SLAVE-CAB-8400>S Paralleling Cable, S-Series to S-Series/SBS-8400/SBS-4815
SLAVE-CAB-8400>(2)S Paralleling Cable, S-Series to (2) S-Series/SBS-8400/SBS-4815
BCT110/220-1000 750 Watt Voltage Transformer 110/220 Vac 50/60 Hz
Pelican case upgrade available for select models