Main Battery Disconnect Switches

  • Bus voltages 24vdc to 480vdc nominal
  • Capacities from 100A to 4000A
  • Fusible or molded case circuit breakers (UL489)
  • NEMA 1 enclosures, wall mount or floor mount
  • 24v UVR, Aux NO/NC, 120V Shunt Trip & EPO interface as standard
  • Designed for all applications including UL1778 UPS
Main Battery Disconnect Switch
 Main Battery Disconnect Drawing (400A example) pdf  
   
   
   
   

 

 

SBS MAIN BATTERY DISCONNECT SELECTION & PRICING

 

DC AMPS

NOMINAL

CONFIGURATION NUMBER

UNDER-VOLTAGE

POLES

ENCLOSURE

AUX

SHUNT

 

 

Vdc BUS

 

 RELEASE

 

 

CONTACT

TRIP

 

 

100

<240v

SEDA24AT0150TE100-ST-UV-B1

24vdc/vac

2

NEMA1

1

120/60

 

 

150

(120 cells)

SEDA24AT0150TE150-ST-UV-B1

24vdc/vac

2

NEMA1

1

120/60

 

 

250

240 vdc

SFHA24AT0250SF250-ST-UV-B1

24vdc/vac

2

NEMA1

1

120/60

 

 

400

 

SGHA26AT0400SG400-ST-UV-B1

24vdc/vac

2

NEMA1

1

120/60

 

 

600

 

SGHA26AT0600SG600-ST-UV-B1

24vdc/vac

2

NEMA1

1

120/60

 

 

800

 

SGHA26AT0800SG600-ST-UV-B1

24vdc/vac

2

NEMA1

1

120/60

 

 

1200

 

SGHA26AT01200SK1200-ST-UV-B1

24vdc/vac

2

NEMA1

1

120/60

 

 

 

 

 

 

 

 

 

 

 

 

100

>240v

SEHA36AT0150TE100-ST-UV-B1

24vdc/vac

3

NEMA1

1

120/60

 

 

150

(240 cells)

SEHA36AT0150TE150-ST-UV-B1

24vdc/vac

3

NEMA1

1

120/60

 

 

250

480vdc

SFHA36AT0250SF250-ST-UV-B1

24vdc/vac

3

NEMA1

1

120/60

 

 

400

 

SGHA36AT0400SG400-ST-UV-B1

24vdc/vac

3

NEMA1

1

120/60

 

 

600

 

SGHA36AT0600SG600-ST-UV-B1

24vdc/vac

3

NEMA1

1

120/60

 

 

800

 

SGHA36AT0800SG600-ST-UV-B1

24vdc/vac

3

NEMA1

1

120/60

 

 

1200

 

SGHA36AT01200SK1200-ST-UV-B1

24vdc/vac

3

NEMA1

1

120/60

 

 

 

 

 

 

 

 

 

 

 

 

All battery disconnects are in UL NEMA 1 enclosure with a UL890 circuit breaker rated for 250vdc nominal,  and have both a 120/60 Shunt Trip Module (Liebert & Default) or a 24v S.T. Module (Powerware, Specify), 24Vac/dc Under-Voltage Release Module (MGE, Mitsubishi, Default) and one auxilliary contact N/C, (Default).  Two pole circuit breakers are suitable for battery systems of 125 cells or less.  Three pole breakers are designed for systems in excess of 125 cells and are to be "Series Connected" to achieve a 500vdc nominal rating.  Series connection requires that the positive conductor be routed through 2 of the 3 breaker poles.  Should you have any questions about this standard dc wiring practice, please contact SBS engineering services at 800-554-2243, xt 3009; or email sbs@sbsbattery.com.  ALWAYS CHECK UPS I&O MANUAL FOR PROPER DC BREAKER RATING.  Consult factory for other configurations.

                   
                   
                   

 

 

 
 
 

 