The SBS UPS Series battery is suitable for all critical power UPS applications including UL924 emergency lighting. Designed with high-density thin plate technology, the UPS battery will deliver up to 30% additional watts per cell than the typical UPS battery of equal footprint.
All jars are flame-retardant ABS (UL94) as standard at no additional cost. The UPS series VRLA battery ensures your optimum longevity, reliability and availability. SBS offers complete replacement services, IEEE testing and redundant battery strings in cabinets or on rack system.
Technical Data |
|||||||
Part No. | Voltage | Watts/ Cell* | Ah Rate** | Length (in.) | Width (in.) | Height (in.) | Terminal Type (Bolt) |
UPS12-35WFR | 12 | 35 | 9 | 5.95 | 2.56 | 3.90 | .250 tab |
UPS12‑100WFR | 12 | 92.8 | 27 | 6.46 | 4.92 | 6.89 | T12 |
UPS12-150WFR | 12 | 150.0 | 35 | 7.68 | 5.12 | 6.57 | T6 |
UPS12-210WFR | 12 | 225.1 | 55 | 9.02 | 5.43 | 7.99 | T6 |
UPS12-300WFR | 12 | 324.6 | 82 | 10.20 | 6.61 | 8.31 | T6 |
UPS12-350WFR | 12 | 370.3 | 95 | 12.00 | 6.61 | 8.27 | T6 |
UPS12-400WFR | 12 | 430.4 | 110 | 12.81 | 6.69 | 8.50 | T8 |
UPS12-540WFR | 12 | 539.0 | 155 | 13.19 | 6.77 | 10.94 | T8 |
UPS6-700WFR | 6 | 681.0 | 210 | 12.7 | 7.00 | 9.10 | T8 |
*15 Min. rate to 1.67 Vpc @ 77F
**Nominal 20 Hr. rate to 1.80 Vpc @ 77F
Comparative UPS Battery Part Numbers |
||||
SBS Part No. | C&D MR-Series | C&D Dynasty-Series | EnerSys HX-Series | Deka/Unigy HR-Series |
UPS12-35WFR | 12HX35 | |||
UPS12-100WFR | UPS12-100FR | 12HX100 | ||
UPS12-150WFR | UPS12-150MR | 12HX135/150 | U1HR1500 | |
UPS12-210WFR | UPS12-210MR | UPS12-200FR | 12HX205 | 45HR2000 |
UPS12-300WFR | UPS12-300MR | UPS12-270FR | 12HX300 | 24HR3000 |
UPS12-350WFR | UPS12-350MR | UPS12-310FR | 12HX350 | 27HR3500 |
UPS12-400WFR | UPS12-400MR | UPS12-370FR | 12HX400 | 31HR4000 |
UPS12-540WFR | UPS12-490/540MR | UPS12-475FR | 12HX505/540 | 31HR5000 |
UPS6-700WFR | UPS6-620MR | UPS6-620FR | 6HX800 |
UPS High Rate Battery, 12 Volt VRLA Battery
150 Watts per cell (15 Min. rate to 1.67 V/cell @ 77°F)
35 AH (20 Hr. rate to 1.80 V/cell @ 77°F)
UPS High Rate Battery, 12 Volt VRLA Battery
370.3 Watts per cell (15 Min. rate to 1.67 V/cell @ 77°F)
95 AH (20 Hr. rate to 1.80 V/cell @ 77°F)
UPS High Rate Battery, 12 Volt VRLA Battery
92.8 Watts per cell (15 Min. rate to 1.67 V/cell @ 77°F)
27 AH (20 Hr. rate to 1.80 V/cell @ 77°F)
UPS High Rate Battery, 12 Volt VRLA Battery
539 Watts per cell (15 Min. rate to 1.67 V/cell @ 77°F)
155 AH (20 Hr. rate to 1.80 V/cell @ 77°F)
UPS High Rate Battery, 6 Volt VRLA Battery
681 Watts per cell (15 Min. rate to 1.67 V/cell @ 77°F)
210 AH (20 Hr. rate to 1.80 V/cell @ 77°F)
UPS High Rate Battery, 12 Volt VRLA Battery
324.6 Watts per cell (15 Min. rate to 1.67 V/cell @ 77°F)
82 AH (20 Hr. rate to 1.80 V/cell @ 77°F)
UPS High Rate Battery, 12 Volt VRLA Battery
225.1 Watts per cell (15 Min. rate to 1.67 V/cell @ 77°F)
55 AH (20 Hr. rate to 1.80 V/cell @ 77°F)
UPS High Rate Battery, 12 Volt VRLA Battery
430.4 Watts per cell (15 Min. rate to 1.67 V/cell @ 77°F)
110 AH (20 Hr. rate to 1.80 V/cell @ 77°F)
UPS High Rate Battery, 12 Volt VRLA Battery
34.8 Watts per cell (15 Min. rate to 1.67 V/cell @ 77°F)
9 AH (20 Hr. rate to 1.80 V/cell @ 77°F)