Single Phase 24/48/130 Vdc, 6/12/20/25/50 Amp Float Chargers
The EC Series chargers are microprocessor controlled, easy to setup and easy to operate via a user-friendly LCD screen. These highly reliable chargers include many standard features including: filtering (battery eliminator), internal temperature compensation, local alarms with indication on the LCD screen, summary alarm via Form C relay, a summary alarm buzzer, a ground pad plus many more.
The single phase EC Series chargers are available from 24 to 130 Vdc and rated from 6 to 50 Amps. They are compatible with flooded lead-acid (FLA), valve-regulated lead-acid (VRLA) and nickel-cadmium (NiCd) battery systems.
Common/summary Form C alarm contact/relay on main control board for DC fail, high Vdc, low Vdc, DC fail, high Vac, low Vac, pos/neg ground fault and end of discharge alarms
Summary alarm buzzer
All alarms can be disabled
High/Low DC voltage shutdown
Manual or automatic 1–255 hr. equalize timer
Push button (Hold to Equalize) mode selection
Ground terminal lug
Controls can be disabled for security
AC & DC surge suppressors
Universal control board
NEMA 1 enclosure with sprinkler resistant ventilation
ANSI 61 gray powder coated finish
All chargers are stackable and floor, wall or shelf mountable
Bottom/side cable entry
Full 5 year warranty
Made in USA!
*100mVrms for 130 Vdc models. Meets or exceeds NEMA PE5-1996 requirements.
Available Options
Alarm board with NO/NC individual Form C alarm contacts/ relays. Includes: Summary, DC fail, high Vdc, low Vdc, high Vac, low Vac, pos/neg ground fault (combined) and end of discharge alarms
Remote temp. comp. cable/sensor (10 ft. or 25 ft.)