Hydrogen Sensor and Monitoring System

The SBS-H2 Hydrogen Detector is a complete hydrogen monitoring system with visual and audible alarms.The system comes complete with the main display, a highly accurate hydrogen gas sensor and a 25-ft. cable.

 

Lead-acid storage batteries emit hydrogen gas while discharging and recharging. Hydrogen concentrations of 4% to 75% by volume in air are potentially explosive. The SBS hydrogen gas detector is designed to allow dissipation and give warning before any concentration reaches the lower explosive limit (LEL) of 4%.  This unit is very easy to install and very cost effective.

 

This device can be used to meet the minimum requirements for your battery room to be in compliance with IEEE Std 484-2002, National Fire Protection Agency (NFPA) Article 64 and Uniform Building Code (UBC) Sect 6400.  Failure to monitor hydrogen gas production and alarm when certain thresholds are reached can void your insurance policy and exposes your company to severe risk should any injury result from a non-passive hydrogen gassing event.

 

Benefits

  • The True Hydrogen Gas Detector - single gas detection (H2) to eliminate false positives from other gases such as butane, ethanol, and hydrocarbons in the air
  • Can be wired to initiate exhaust fan when 1% hydrogen is detected
  • Unit will alarm at 2% and can be linked to alarm system
  • SBS exclusive
  • Modular design detector does not require complete replacement for repairs or calibrations
  • Dual AC or DC power supply connections
  • UL / CE Certified Hydrogen Sensor for installations & hazardous locations
  • Ideal for remote locations
  • H2 display allows for a 2nd sensor input to increase coverage area
  • Provides coverage redundancy in large monitoring spaces
  • Protects life, property and company profits

 

Features

  • Universal power inputs: 110/220 Vac or 12-48 Vdc input
  • Wall or 2-gang junction box mountable
  • Mechanical relays are easily accessible:
  • · Max Switching voltage 28 Vdc, 277 Vac
  • · Rated Current 10A @ 277 Vac, 15A @ 125 Vac
  • Push button diagnostic test
  • Hydrogen sensor is UL Class 1 Division 2, ATEX, and CE certified for hazardous locations
  • Sensor has a temperature rating of -4° F to 176° F
  • Display can be calibrated in the field with p/n H2-CALKIT option
  • Can operate in a wide range of temperatures and humidity
  • Audible alarm

 

Includes

  • Main body/display
  • Hydrogen sensor
  • 25 ft. cable

 

 

Operation

Warning Settings: When 1% hydrogen is present in the air the yellow warning light will come on and the warning relay contact will close, allowing power to peripherals, such as a vent fan or other devices.

 

Alarm Settings: When at least 2% hydrogen is present in the air, the red warning light will come on and an audible alarm activates. In addition, a second alarm relay contact will close, which can be used to shut down the system and initiate a building alarm system or other devices.

 

hydrogen gas detection system for battery rooms

 

 

Resources

  - SBS-H2 Data Sheet

  - SBS-H2 User's Manual

  - SBS-H2 Startup Instructions

  - SBS-H2 Calibration

  - SBS-H2 Wiring Schematic

  - SBS-H2 MSDS

  - White Paper on Best Practices

 

 

SBS-H2 detector/sensor

 

 

Calculate Your Ventilation Requirements Here

 

 

 

Applications

  • Substations
  • Battery rooms
  • Uninterruptible power supply (UPS)
  • Battery cabinet systems
  • Battery charging areas
  • Hydrogen fueled back-up power systems

 

 

 

 

 

 

 

 

 

Read article: Hazards of unmonitored hydrogen in battery installations


 

 

 

 

 

 

Detector can operate exhaust fans and building alarms / SCADA systems:

battery hydrogen sensor diagram

SBS-H2 hydrogen sensor and detector's calibration kit accessory

 

 

Accessories & Mounting

Unit can be calibrated in the field with p/n H2-CALKIT option.

hydrogen sensor with cable

 

Additional hydrogen sensor with 25 ft. cable. (Also, 50 ft. and 100 ft. cables are available.)

hydrogen detector mounted with junction box

 

Unit can be powered with either AC or DC power and can be mounted directly to a wall or to an electrical box, making it extremely versatile and user-friendly. Additional mounting options in data sheet.

 

 

Sample Hydrogen Scenarios of Hydrogen Detector Placement

SBS-H2: Stationary Hydrogen Gas Detector Placement Location

SBS-H2: Forklift Battery Hydrogen Gas Detector Placement Location

 

The SBS-H2 includes relays for remote connection to alarm/monitoring systems and for control of external relays or an exhaust fan.

 

SBS will soon be offering the SBS-H2CA, specifically designed to meet the California/OSHA Article 109, Subarticle 5185 requirement.

 

Ordering Information

Part No. Description
SBS-H2 Hydrogen Detector Package

 

Accessory Ordering Information

Part No. Description
H2-SENSOR Additional hydrogen sensor with 25 ft cable
H2-CALKIT Calibration kit
H2-JB 4 11/16" x 4 11/16" 2-gang junction box
H2-50FT-CABLE 50 ft cable (no hydrogen sensor)
H2-100FT-CABLE 100 ft cable (no hydrogen sensor)
E190399 AC Cord 110V, 10A, 10 ft with plug

 

Specifications

1% Hydrogen Energizes a relay which can activate exhaust fan or SCADA system/alarm
2% Hydrogen Sounds audible alarm and energizes relay which can be used on SCADA system
Power Source 110 / 220 Vac, 50/60 Hz OR
12-48 Vdc (9-60 Vdc operating voltage)
Size 4.75" L x 5.25" W x 1.4" D (main body/display)